Sound Check (UK)

This guide applies to the heatpunk.co.uk version of Heatpunk. The information provided here does not apply to heatpunk.ie.

The sound check is part of the Heat Pump task and helps determine whether the planned installation position will generate excessive noise that could disturb neighbouring properties. The results of the sound check will be displayed in the customer proposal and technical reports. 

Completing the sound assessment

When you create a new project you will be prompted to complete the sound check when you navigate to the heat pump task.

To edit the details of the sound check click the pencil icon to the top right of the results.

Choosing a method

There are currently two sound assessment calculation methods published by MCS. England's Permitted Development Rights now require you to use the 2025 calculation method which is based on MCS 020 a). Other UK nations, where they have not changed their Permitted Development Rights, may still require you to use the legacy calculation method based on MCS 020. Please contact your local planning authority if you are unsure which method to use. 

When you start the sound check for your project you can choose between the 2025 calculation method or the legacy calculation method.

image.png

Using the 2025 calculation method - MCS 020 a)

To comply with MCS 020 a), the calculated noise level at each assessment position must be below 37 dB. Under MCS 020 a), it is vital to include multiple assessment positions, as more distant locations without a barrier may experience higher noise levels than closer positions that are shielded. 

See MCS guidelines for further information on the calculation.

image.png

Using the legacy calculation method - MCS 020

To comply with the legacy MCS 020 standard, the noise level at a single assessment position must be below 42 dB. 

See MCS guidelines for further information on the calculation.

image.png