How is the outdoor design temperature (ODT) set and can I change it?
To change the ODT for your project follow these steps:
An additional 0.3°C will need to be removed for every 50 m above sea level, with altitude given in the input section of the technical report & customer proposal.
Note this will not affect the Outdoor Low Temperature (ODL) used in the performance task, since this follows MCS 031 which states the the ODL from Appendix A must be used. The ODL is not the same as the ODT used for the design, which you may adjust within MCS rules stated in MIS 3005-d.