Error: Couldn't get heat pump capacity: ODT out of range

The performance task uses an ODL (outdoor low temp) which is lower than the standard project ODT in Heatpunk. This can mean it works fine in the heat pump task but then there is an issue in performance. 

image.png

To solve this,  go to the heat pump in My Components. You will need to ensure that the table goes down to -7 degrees to make sure it works in every location. You should be able to find the values in the datasheet.